Airport Hotel Laundry Facility

Quarterly service on a hotel laundry's BOGE C7.5L compressor, Keltec KRAD-40 dryer, and C-Aire tank included correcting transformer wiring left unchanged during a motor voltage conversion.

Industry
Industrial Laundry Operation for Hotel
Service Type
Quarterly Preventative Maintenance
Equipment
BOGE C7.5L Rotary Screw Air Compressor
Keltec KRAD-40 Refrigerated Dryer
C-Aire Tank
BOGE C7.5L Rotary Screw Air Compressor installed at Airport Hotel Laundry Facility

The problem

The laundry used a BOGE C7.5L, Keltec dryer, and C-Aire tank for pressing equipment and maintenance. A previous contractor had converted the motor from 230V to 460V without rewiring the transformer, so fuses kept tripping. The equipment also needed to run quietly near guest areas.

The work

We rewired the transformer for 460V and replaced the blown fuses. Quarterly maintenance included an oil change, new oil and air filters, a Tsunami separator filter, and a replacement thermal valve and sensor. We changed the scavenge line screen, checked flow through the stone, serviced the solenoid, and cleaned and lubricated the inlet and minimum pressure valves. The cooler and cabinet were cleaned before testing.

Services Performed

  • Diagnosed and rewired transformer (electricians had rewired motor from 230V to 460V but did not rewire transformer, causing fuses to trip)
  • Replaced fuses
  • Blew out cooler and unit
  • Replaced thermal valve and sensor
  • Oil change
  • Replaced oil filter
  • Replaced air filter
  • Replaced Tsunami separator filter
  • Changed scavenge line screen and verified flow through stone
  • Serviced solenoid
  • Cleaned and re-lubed inlet and MP valve
  • Wiped down unit

The outcome

The corrected wiring stopped the fuses from tripping. Quiet compressed air service was restored for round-the-clock laundry and maintenance work, within the hotel's guest comfort standards.