Senior Living Facility Fire Protection System
1993 C-Aire S175 Baseplate Fire Protection Air Compressor
Quarterly service on a hotel laundry's BOGE C7.5L compressor, Keltec KRAD-40 dryer, and C-Aire tank included correcting transformer wiring left unchanged during a motor voltage conversion.

The laundry used a BOGE C7.5L, Keltec dryer, and C-Aire tank for pressing equipment and maintenance. A previous contractor had converted the motor from 230V to 460V without rewiring the transformer, so fuses kept tripping. The equipment also needed to run quietly near guest areas.
We rewired the transformer for 460V and replaced the blown fuses. Quarterly maintenance included an oil change, new oil and air filters, a Tsunami separator filter, and a replacement thermal valve and sensor. We changed the scavenge line screen, checked flow through the stone, serviced the solenoid, and cleaned and lubricated the inlet and minimum pressure valves. The cooler and cabinet were cleaned before testing.
The corrected wiring stopped the fuses from tripping. Quiet compressed air service was restored for round-the-clock laundry and maintenance work, within the hotel's guest comfort standards.