Church Fire Protection System in Medina, MN

Pump replacement, belt adjustment, and a pressure-switch wiring repair for a Medina church's fire protection compressor.

Industry
Dry Pipe Fire Sprinkler Systems
Service Type
Pump Replacement, Belt Repair & Electrical Diagnosis
Equipment
C-Aire S900 Fire Protection Compressor
C-Aire S900 Fire Protection Compressor installed at Church Fire Protection System in Medina, MN

The problem

The dry pipe sprinkler compressor was reported to be humming and had shown belt and pump issues. The system needed diagnosis, repair, and repeated pressure cycling before it could be trusted for normal fire protection operation.

The work

We diagnosed and replaced the failed pump, corrected belt fit and tension, and checked the motor under load. A broken pressure-switch wire was repaired, followed by repeated compressor cycles to verify pressure control.

Services Performed

  • Diagnosed pump and belt issue
  • Replaced compressor pump
  • Installed correct belt
  • Adjusted belt tension
  • Checked motor operation under load
  • Repaired pressure switch wiring
  • Cycled compressor repeatedly
  • Verified operating pressure

The outcome

The compressor started normally, loaded within expected motor readings, cycled to operating pressure, and was returned to service with the backup unit disconnected from the system.